Generator Sizing Calculator

Written byupdated

Extra power for starting the largest motor — a pump, compressor or fridge. The starting current is on the appliance's rating plate or datasheet.

Result

  • Generatorat least 6.3 kVA — the start-up decides
  • Required, kVA4.5
  • Required, kW3.6
  • Peak load, W5,000
  • Peak, kVA6.25
  • Working

    3,000 × 1.2 ÷ 0.8 = 4,500 VA; (3,000 + 2,000) ÷ 0.8 = 6,250 VA