Voltage Drop Calculator
Written byOleh Soloninupdated
Russia's GOST 29322-2014 (IEC 60038) sets 230/400 V; on a three-phase line enter the phase voltage here too, 230 or 220 V.
Advanced options
0.8 is the figure IEC 60364-5-52 tells you to use when nothing better is known; a heater is 1.
Result
- Voltage drop, V11.6
- Drop, %5.04%
- Verdict
Over 5% for other loads (supplied from the public network, IEC 60364-5-52, table G.52.1) — a larger cross-section is needed
- Phase voltage at the load, V218.4
- Standard area within the limit, mm²4
- Cross-section
The exact figure is 2.52 mm²; the next standard IEC 60228 size is 4 mm².
- Heat in the conductors, W230.4
- Working
u = 2 × (0.0225 × 50 ÷ 2.5 × 0.8 + 0.00008 × 50 × 0.6) × 16 = 11.6 V; 11.6 ÷ 230 = 5.04%