Voltage Drop Calculator

Written byupdated

Russia's GOST 29322-2014 (IEC 60038) sets 230/400 V; on a three-phase line enter the phase voltage here too, 230 or 220 V.

Advanced options

0.8 is the figure IEC 60364-5-52 tells you to use when nothing better is known; a heater is 1.

Result

  • Voltage drop, V11.6
  • Drop, %5.04%
  • Verdict

    Over 5% for other loads (supplied from the public network, IEC 60364-5-52, table G.52.1) — a larger cross-section is needed

  • Phase voltage at the load, V218.4
  • Standard area within the limit, mm²4
  • Cross-section

    The exact figure is 2.52 mm²; the next standard IEC 60228 size is 4 mm².

  • Heat in the conductors, W230.4
  • Working

    u = 2 × (0.0225 × 50 ÷ 2.5 × 0.8 + 0.00008 × 50 × 0.6) × 16 = 11.6 V; 11.6 ÷ 230 = 5.04%

Related tools

Wire Size Calculator

Picks a cable cross-section for a given current, allowing for conductor material and installation method.

Watts to Amps and Amps to Watts

Converts watts and kilowatts to amps and back on 220 and 380 V AC and 12 or 24 V DC, shows the amps per kilowatt, and suggests a breaker no smaller than the current from the IEC 60898-1 range.

Three-Phase Power Calculator

Real, apparent and reactive power for a three-phase supply from line voltage, current and power factor.